Restricted earth fault relay - JRD 011/013

Features

  • Software based design
  • Very sensitive and wide setting range
  • Insensitive to currents at harmonic frequencies
  • Trip test facility

Application:

Restricted earth fault protection of transformers, generators and motors differential protection of bus bars, motors and generators.

Principle of Operation:

Type JRD 011 & JRD 013 are basically a current operated, software based, differential relays which works on the high impedance principle. An external series stabilizing resistor is used with this relay to make it a voltage operated relay. The voltage setting of the relay is adjusted to be higher than that developed by the current transformers used maximum external fault conditions.JRD 011 is a single pole relay where as JRD 013 is a triple pole relay.

The fundmental frequency. The output of the filter is fed to a voltage comparator. When the sensing current signal at the fundamental frequency exceeds the set value, the comparator gates a train of pulses to the processor. The program residing in the CPU (central processing unit) performs the function of control and also gives output signals for relay and LED ( Light Emitting Diode) driver circuits. The operation of the relay is indicated by the glowing of a 'Red' LED , which has to be reser manually by means of a 'RESET' push button provided on the front of the relay. A 'Trip Test' push button is also provided in the relay to enable testing of the trip and alarm circuits.

The relay will not operated at third harmonic currents upto 25 times the setting.

ACCURACY:

Operating value : ± 5%
Operating Time : ± 5% or ± 30ms

RATINGS:

Current rating : 1A / 5A
Auxiliary Supply : 1) 20 to 60V DC
  : 2) 75 to 150V DC / AC
  : 3) 175 to 300V DC / 185 to 250V A

CONTACT RATINGS:

Contact 1 & 2 : 10A at 24V DC / 230V AC

CONTACT DURABILITY :

Unloaded contact : 1,000,000 Operations
Loaded contact : 100,000 Operations

MECHANICAL DESIGN :

Weight : App. 1.5kg
Case Size : 144 sq. mm
Installation : Flush mounting
Panel cutout : 138mm x 138mm

STANDARD COMPLIANCE:

Accuracy Test : IEC 60255-3
Insulation Test : IEC 60255-5

SETTINGS:

Operating value : 2.5 to 80% of in steps of 2.5%

IMPEDANCE:

1A rated : 200milli Ohms
5A rated : 20milli Ohms

EXTERNAL STABILIZING RESISTOR:

1A rated : 0 – 600Ώ 100W adjustable
5A rated : 0 – 100Ώ 100W adjustable

OVER LOAD RATINGS:

Current input : 2 times Rated continuous
5A rated : 20 times Rated for 3s

BURDEN :

Current input   : Less than 0.2VA at rated 1A
  : Less than 0.5VA at rated 5A
Auxiliary Supply : Less than 3W (Non operated)
  : Less than 6W (Operated)

ORDERING INFORMATION :

Current rating : 1A / 5A
Relay type : JRD 011 (One pole)
  : JRD 013 (Three pole)
Auxiliary supply : 1) 20 to 60V DC
  : 2) 75 to 150V DC / AC
  : 3) 175 to 300V DC / 185 to 250V AC