Programmable directional inverse time current relay - JRP XXX
Features
- Software based design
- Programmable time current characteristics
- Choice of four curves
- Selectable characteristic angle
- Programmable directional / Non-directional element
- Draw - out case
Application:
The relay provides time graded phase and earth fault
protection of Parallel transformers, Transformer feeders,
Parallel feeders, ring main system etc.,
Principle of Operation:
The relay measures the line current from each of the phases and if it exceeds the set threshold, then relay
extends a trip signal after an operating time. The relay's operating time is determined by selecting one of the four inverse time characteristics. The relay has facility to active / inhibit the high set protection
feature. The relay output contacts are self reset . Relay operation without any fault current is determined by trip test facility.
ACCURACY:
| Operating value |
: |
105% to 120% of setting |
| Drop-off / pick-up |
: |
Between 80% to 95% |
| Operating Time |
: |
±5% or ±30ms whichever is higher |
| High set operating value |
: |
±5% or ±30ms whichever is higher |
| Phase angle |
: |
±9º of the operating angle |
| High set operating time |
: |
Less than 30ms @ 2 times current setting |
| Reset Time |
: |
160ms to 180ms |
RATINGS:
| Current rating ( In ) |
: |
1A / 5A |
| Auxiliary Supply |
: |
1) 20 to 60V DC |
| |
: |
2) 75 to 150V DC / AC |
| |
: |
3) 175 to 300V DC / 185 to 250V A |
CONTACT RATINGS:
| Relay rating |
: |
10A at 24V DC/230V AC |
CONTACT DURABILITY :
| Loaded contact |
: |
10,000 operations min. |
| Unloaded contact |
: |
100,000 operations min. |
MECHANICAL DESIGN :
| Weight |
: |
2500 gms. (approx) |
| Case Size |
: |
144sq mm, depth 232mm |
| Installation |
: |
Flush mounting |
| Panel cutout |
: |
138mm x 138mm |
INSULATION:
| 1. 2KV RMS, 50 Hz for 1 minute / 2.5 KV for 1 sec . Between all terminals and earth. |
| 2. 1KV RMS, 50 Hz for 1 minute across open contacts as per IEC 60255-5 |
STANDARD COMPLIANCE:
| Accuracy Test |
: |
IEC 60255-3 |
| Insulation Test |
: |
IEC 60255-5 |
|
SETTINGS:
| Operating characteristics |
: |
1) 3.0s Normal Inverse |
| |
: |
2) 1.3s Normal Inverse |
| |
: |
3) 1.5s Very Inverse |
| |
: |
4) 0.8s Extremely Inverse |
| Phase O/c (IDMT) |
: |
50 to 200% in steps of 10% |
| Earth fault (IDMT) |
: |
5 to 80% in steps of 5% |
| TMS (separate for O/c & E/F) |
: |
0.1 to 1.0 in steps of 0.01 |
| Phase Hi-set |
: |
200 to 3200% in steps of 200% |
| Earth fault Hi-set |
: |
50 to 800% in steps of 50% |
Char. Angel setting :
| O/C setting |
: |
Lead 30º |
| |
: |
Lead 45º |
| |
: |
Lead 60º |
| E/F setting |
: |
Lag 12.5º |
| |
: |
Lag 30º |
| |
: |
Lag 45º |
OVER LOAD RATING: |
|
|
| Current input |
: |
2 times rated continuous |
| |
: |
20 times rated for 3 sec |
BURDEN :
| Current input |
: |
0.2VA per phase (rated 5A) |
| |
: |
0.05VA per phase (rated1A) |
| Aux. Supply |
: |
Less than 8W (Non operated) |
| |
: |
Less than 10W (Operated) |
ORDERING INFORMATION :
| Relay rating type |
: |
JRP 011(O/c relay) |
| |
: |
JRP 012 (O/c with hiset relay) |
| |
: |
JRP 021 (E/F relay) |
| |
: |
JRP 022 (E/F with hiset relay) |
| Current rating |
: |
1A / 5A |
| Aux supply |
: |
20 to 60V DC |
| |
: |
75 to 150V DC / AC |
| |
: |
175 to 300V DC / 185 to 250V AC |
|