Over Current Relay - 9XX

Features

  • Software based design
  • DIP switch settings
  • Choice of four curves
  • Instantaneous high set
  • Very low burden

Application:

Time graded protection of generators, Transformers, capacitors etc;









ACCURACY:

Operating value   : 105 to 120% of set current
Resetting value : 80 to 97% of the pickup value
High set operating value : ±5%
Inverse operating time : ±5% or ± 30ms (which ever is higher)
High set operating time : < 40ms @ 2 times the set current
Reset time : 200 to 250ms
Over shoot time : Less than 100ms

RATINGS:

Current rating (In) : 1A or 5A
Auxiliary Supply : 20 to 60V DC or
  : 80 to 260V AC/DC

CONTACT RATINGS:

For JRC 951P,JRC 952,JRC 962P, JRC 964 relays : Trip – 10A at 24V DC/ 230V AC
: Alarm – 5A at 24V DC/ 230V AC
For JRC 953 & JRC 966 relays  : 5A at 24V DC/230V AC

OUTPUT CONTACTS:

For JRC 951P,JRC 952, JRC 962P,JRC 964 relays : Trip – 1N/O
: Alarm –2N/O
For JRC 953 & JRC 966 relays  : 2N/O contacts

MECHANICAL DESIGN :

Weight : 550gms approx.
Case Size : 96sqmm, Depth 105mm
Installation : Flush mounting
Panel cutout : 92mm x 92mm

STANDARD COMPLIANCE :

Accuracy test   : IEC 60255-3 
Insulation test  : IEC 60255-5
1MHz HFD test : IEC 60255-22-1

CURRENT SETTING (INVERSE TIME):

Over current (I>) : 50 to 200% in steps of 10%
     
Instantaneous high set : 2 to 16 times 1> set value
     

OPERATING CHARACTERISTICS:

Inverse time Characteristics    : 3s Normal inverse
  : 1.3s Normal inverse
  : 1.5s Very inverse
  : 0.8/0.6s Extremely inverse
Time multiplier setting (TMS) : 0.01 to 1.6 in two ranges
  : 1st range : 0.01to 0.32 in steps of 0.01
  : 2nd range : 0.05 to 1.6 in steps of 0.05

OVER LOAD RATING:

   
Current input : 2 times the rated continuously
  : 20 times the rated for 3s

BURDEN :

Auxiliary circuit : 3W (Non-operated)
  : 6W ( Operated)
Current input circuit : 1A – 0.05 VA (max) at rated current
  : 5A – 0.2 VA (max) at rated current

ORDERING INFORMATION :

Current rating : 1A or 5A
Curve selection : 0.8 or 0.6s Extremely inverse   
Relay type : JRC 966 - 3 Pole IDMT With High set
  : JRC 953 - 3 Pole IDMT Without High set
  : JRC 964 - 2 Pole IDMT With High set
  : JRC 952 - 2 Pole IDMT Without High set
  : JRC 962P - 1 Pole IDMT With High set
  : JRC 951P - 1 Pole IDMT Without High set
Auxiliary Supply : 20 to 60V DC or 80 to 260V AC/DC