Over Current Relay - 9XX
Features
-
Software based design
-
DIP switch settings
-
Choice of four curves
-
Instantaneous high set
-
Very low burden
Application:
Time graded protection of generators, Transformers, capacitors etc;
ACCURACY:
| Operating value |
: |
105 to 120% of set current |
| Resetting value |
: |
80 to 97% of the pickup value |
| High set operating value |
: |
±5% |
| Inverse operating time |
: |
±5% or ± 30ms (which ever is higher) |
| High set operating time |
: |
< 40ms @ 2 times the set current |
| Reset time |
: |
200 to 250ms |
| Over shoot time |
: |
Less than 100ms |
RATINGS:
| Current rating (In) |
: |
1A or 5A |
| Auxiliary Supply |
: |
20 to 60V DC or |
| |
: |
80 to 260V AC/DC |
CONTACT RATINGS:
| For JRC 951P,JRC 952,JRC 962P, JRC 964 relays |
: |
Trip – 10A at 24V DC/ 230V AC
|
|
: |
Alarm – 5A at 24V DC/ 230V AC
|
| For JRC 953 & JRC 966 relays |
: |
5A at 24V DC/230V AC |
OUTPUT CONTACTS:
| For JRC 951P,JRC 952, JRC 962P,JRC 964 relays |
: |
Trip – 1N/O
|
|
: |
Alarm –2N/O
|
| For JRC 953 & JRC 966 relays |
: |
2N/O contacts |
MECHANICAL DESIGN :
| Weight |
: |
550gms approx. |
| Case Size |
: |
96sqmm, Depth 105mm |
| Installation |
: |
Flush mounting |
| Panel cutout |
: |
92mm x 92mm |
STANDARD COMPLIANCE :
| Accuracy test |
: |
IEC 60255-3 |
| Insulation test |
: |
IEC 60255-5 |
| 1MHz HFD test |
: |
IEC 60255-22-1 |
|
CURRENT SETTING (INVERSE TIME):
| Over current (I>) |
: |
50 to 200% in steps of 10% |
| |
|
|
| Instantaneous high set |
: |
2 to 16 times 1> set value |
| |
|
|
OPERATING CHARACTERISTICS:
| Inverse time Characteristics |
: |
3s Normal inverse |
| |
: |
1.3s Normal inverse |
| |
: |
1.5s Very inverse |
| |
: |
0.8/0.6s Extremely inverse |
| Time multiplier setting (TMS) |
: |
0.01 to 1.6 in two ranges |
| |
: |
1st range : 0.01to 0.32 in steps of 0.01 |
| |
: |
2nd range : 0.05 to 1.6 in steps of 0.05 |
OVER LOAD RATING: |
|
|
| Current input |
: |
2 times the rated continuously |
| |
: |
20 times the rated for 3s |
BURDEN :
| Auxiliary circuit |
: |
3W (Non-operated) |
| |
: |
6W ( Operated) |
| Current input circuit |
: |
1A – 0.05 VA (max) at rated current |
| |
: |
5A – 0.2 VA (max) at rated current |
ORDERING INFORMATION :
| Current rating |
: |
1A or 5A |
| Curve selection |
: |
0.8 or 0.6s Extremely inverse |
| Relay type |
: |
JRC 966 - 3 Pole IDMT With High set |
| |
: |
JRC 953 - 3 Pole IDMT Without High set |
| |
: |
JRC 964 - 2 Pole IDMT With High set |
| |
: |
JRC 952 - 2 Pole IDMT Without High set |
| |
: |
JRC 962P - 1 Pole IDMT With High set |
| |
: |
JRC 951P - 1 Pole IDMT Without High set |
| Auxiliary Supply |
: |
20 to 60V DC or 80 to 260V AC/DC |
|