|
|
Neutral unbalance current relay - JRC122/124
Features
- Software based design
- Instantaneous/Definite time
- Insensitive to harmonics
- Wide setting ranges
- Trip test facility
Application:
Neutral unbalance current protection of double star capacitor banks with floating neutral.
Principle of Operation:
The sensing current is converted to voltage by an internal resistor and this voltage is fed to a harmonic network which is tuned to fundamental frequency. The output of filter is fed to voltage comparator. When the sensing current signal at the fundamental frequency exceeds the set value,the comparator gates a train of pulses to the processor. The program residing in the CPU performs the function of control and also gives output signals for relay and LED driver circuits. The operation of the relay is indicated by the glowing of a 'Red' LED,which has to be reset manually by means of a 'RESET' push button provided on the front of the relay. A 'Trip Test' push button is also provided in the relay to enable testing of the trip and alarm circuits. When this push button is pressed,the output element of the relay is energized and its contacts close to energize trip and alarm circuits
ACCURACY:
| Operating value |
: |
± 5% |
| Drop-off / pick-up |
: |
Between 80% to 95% |
| Operating Time |
: |
±5% or ±30ms whichever is higher |
RATINGS:
| Current rating ( In ) |
: |
1A / 5A |
| Aux. Supply |
: |
1) 20 to 60V DC |
| Breaker close relay |
: |
2) 75V to 150V AC/DC |
| |
: |
3) 175 to 300V DC |
| |
: |
185 to 250V AC |
CONTACT RATINGS:
| Relay rating |
: |
10A at 24V DC/230V AC |
| Contacts configuration |
: |
2 C / O contacts |
CONTACT DURABILITY :
| Loaded contact |
: |
10,000 operations min. |
| Unloaded contact |
: |
100,000 operations min. |
INSULATION:
| 1. 2KV RMS, 50 Hz for 1 minute / 2.5 KV for 1 sec .Between all terminals and cases . |
| 2. 1 KV RMS, 50 Hz for 1 minute across open contacts |
STANDARD COMPLIANCE:
| Accuracy Test |
: |
IEC 60255-3 |
| Insulation Test |
: |
IEC 60255-5 |
MECHANICAL DESIGN :
| Weight |
: |
750gms. (approx) |
| Case Size |
: |
144 Sq mm depth 117 mm |
| Installation |
: |
Flush mounting |
| Panel cutout |
: |
138mm x 138mm |
|
SETTINGS:
| Setting range |
: |
.5% to 80% of rated current in steps of 2.5%. |
| Instantaneous |
: |
Less than 40 milli seconds. |
| Definite time |
: |
to 25 seconds adjustable in steps of 0.1 second. |
| Rejection ratio of 3rd harmonic to |
: |
25 : 1.The relay will not operate at third harmonic |
| fundamental frequency |
|
currents up to 25 times the setting. |
OVER LOAD RATING: |
|
|
| AC current input |
: |
2 times Rated continuous |
| |
: |
20 times Rated for 3s |
BURDEN :
| AC current input |
: |
0.65VA at Rated 5A |
| |
: |
0.2VA at Rated 1A |
| Aux. Supply |
: |
Less than 6W |
| |
: |
|
ORDERING INFORMATION :
| Relay rating type |
: |
JRC 122 ( Single Stage ) |
| |
: |
JRC 124 ( Two Stage ) |
| Current rating |
: |
1A or 5A |
| Auxiliary supply |
: |
1) 20 to 60V DC |
| |
: |
2) 75 to 150V AC/DC |
| |
: |
3) 175 to 300V DC / 185 to 250V AC |
|