Lead power factory relay - JRR 911

Features

  • Software based design
  • Single phase & 3phase measurement
  • Dust proof enclosure

Application:

JRR 911 is used to trip (dis-connect) capacitor bank from the line during lead power factor in the system.

Principle of Operation:

The R,Y and B-Phase line current input to relay is derived from the line CT. The R,Y and B line voltage scaled to relay rated voltage using transformers. The relay measures the phase angle between R,Y and B phase Current and R,Y and B phase voltage, the output contact operates when PF reaches lead condition after fixed operating time of 60s. The output contact release when PF reaches lag condition after fixed operating delay delay of 60s.

The aux supply is required to power up the unit.

The relay displays power factor, and lag indication.



ACCURACY:

PF : ± 0.02 or ± 2°

RATINGS:

Aux. supply    : 80 – 260V AC/DC
Current : 1A or 5A

CONTACT RATINGS:

Contacts : 5A at 24V DC / 230V AC

CONTACT DURABILITY :

Loaded contact     : 100,000 Operations
Unloaded contact : 1,000,000 Operations

MECHANICAL DESIGN :

Weight : App. 240 grms
Case Size : 96 mm x 96 mm with depth 61 mm
Installation : Flush mounting
Panel cutout : 91 sq mm

SETTINGS:

Over Current : 5 to 200% in steps of 5%
     
Definite time : 50 ms to 1.25 sec in steps of 10 ms
     

OVER LOAD RATING:

   
Current input : 2 times rated continuous
Voltage input : 2 times rated continuous

BURDEN :

Aux. supply   : Less than 6W at 110 V DC Aux. supply
Current input : Less than 0.05VA at rated 1A
Voltage input : Less than 0.2VA at rated voltage

ORDERING INFORMATION :

Current rating : 1A / 5A
Rated voltage : 110V AC
Relay type : JRR 911