Earth leakage relay - JRC XXX

Features

  • Solid state reliability
  • Built in Test facility
  • Very low primary current sensing
  • Core balance current transformer supplied along with the unit

Application:

The relay used for protection of LV/MV distribution systems requiring very high sensitivity for earth faults.

Principle of Operation:

The relay measures the earth leakage current from theCBCT and if it exceeds the threshold, it extends a trip signal after the operating time.







ACCURACY:

Drop-off / pick-up : Between 80% to 95%
Operating Time : ±5% or ±30ms whichever is higher

CONTACT RATINGS:

TRIP / ALARM :  
2 c/o : 5A at 24V DC/ 230V AC
1 c/o : 10A at 24V DC/ 230V AC

CONTACT DURABILITY :

Loaded contact     : 10,000 operations min.
Unloaded contact : 100,000 operations min.

MECHANICAL DESIGN :

Installation : JRC 172 & JRC 173 Flush mounting
  :   JRC 272,273 & 274 Din rail mounting
Panel cutout dimension    
JRC 072 / 073 : 73 X 137 mm (WxH)
JRC 172 / 173 : 43 X 91 mm (WxH)
JRC 272 / 273 / 274 : 78 X 47 mm (WxH)

INSULATION:

1. 2KV RMS, 50 Hz for 1 minute / 2.5 KV for 1 sec . Between all terminals and cases .
2. 1KV RMS, 50 Hz for 1 minute across open contacts

STANDARD COMPLIANCE:

Accuracy Test : IEC 60255-3
Insulation Test : IEC 60255-5

TERMINAL DIAGRAM :

Note :

 Wiring Diagram of relay types are given on request

SETTINGS:

Relay setting :  
JRC 072 : 0.5A to 8.0A in steps of 0.5A
Definite time setting : 1 – 15 sec in steps of 1sec
JRC 073 : 0.3A to 4.8A in steps of 0.3A
Definite time setting : 1 – 15 sec in steps of 1sec
JRC 172 : 0.3A to 1.8A in steps of 0.1A
Definite time setting : 0 – 1.5 sec in steps of 0.1sec
JRC 173 : 0.5A to 8.0A in steps of 0.5A
Definite time setting : 0 – 15 sec in steps of 1.0 sec
JRC 272 : 0.3A – 1A & 3A - 10A
Definite time setting : 0.05 – 0.3s & 0.5 - 3s
JRC 273 : 0.3A – 1A & 3A - 10A
Definite time setting : 0 – 0.5s
JRC 274 : 0.1A – 0.25A & 0.3A - 0.75A
Definite time setting : 0.05 – 0.3s & 0.5 - 3s
Operating characteristics :  
Operating time :  
Instantaneous : Less than 40 milli seconds
Definite time setting : As mentioned above

OVER LOAD RATING:

   
Over load continuous : Withstands continuous primary fault current of 400 A.
Short time : Withstands primary fault current of 1200A for 10seconds

BURDEN :

Aux. Supply : Less than 5W

ORDERING INFORMATION :

Relay rating type : JRC 072,JRC 073,JRC 0172,JRC 0173,JRC 0272,JRC0273
  : JRC 0273,JRC 0274
Aux. Supply : 110V AC, 230V AC,415V AC( only for JRC 072 &73)
Inner diameter of CBCT : 100, 200, 300, 400 mm. are standard for circular CBCTs
  : all dimensions should be given.