Battery earth fault relay - JRC 082
Features
- Software based design
- Instantaneous / Definite time
- Wide range of battery voltage
- Solid state reliability
Application:
The relay monitor the battery and ensure that no leakagebetween battery and ground in DC systems.
Principle of Operation:
The relay measures the leakage current between battery and earth if the current increased more than the set value the relay trips as per time delay setting . The relay output contacts are hand reset type. Relay operation without any fault current is determined by trip test facility.
ACCURACY:
| Operating value |
: |
±5% |
| Operating Time |
: |
±5% or ±30ms whichever is higher |
RATINGS :
| Battery voltage rating |
: |
30V, 48V, 50V, 110V, 220V DC |
| Aux. Supply |
: |
230V AC |
CONTACT RATINGS:
| Trip / Alarm |
:::: |
10A at 24V DC / 230V AC |
CONTACT DURABILITY :
| Loaded contact |
: |
10,000 operations min |
| Unloaded contact |
: |
100,000 operations min |
MECHANICAL DESIGN :
| Weight |
: |
1500 gms. (approx) |
| Case Size |
: |
144sqmm with a depth of 117mm |
| Installation |
: |
Flush mounting |
| Panel cutout |
: |
138mm x 138mm |
STANDARD COMPLIANCE:
| Accuracy Test |
: |
IEC 60255-3 |
| Insulation Test |
: |
IEC 60255-5 |
|
SETTINGS:
| Current setting |
: |
1 to 8mA in steps of 1mA |
| Instantaneous |
: |
< 60ms |
| Definite time |
: |
0.1 to 1.5s in steps of 0.1s |
BURDEN :
| Battery supply |
: |
10W (maximum) |
| |
: |
0.05VA at Rated 1A |
| Aux. Supply |
: |
Less than 8W (Non operated) |
| |
: |
Less than 5W (Operated) |
ORDERING INFORMATION :
| Battery voltage rating |
: |
30V, 48V, 50V, 110V, 220V DC |
| Aux. Supply |
: |
230V AC |
|